AAAC conductor chart to IS 398 (Part 4)

All aluminium alloy conductor (AAAC) codes in IS 398 (Part 4), including the uprated variants, with area, stranding, diameter, mass, breaking load and DC resistance. Select a code and length for the conductor weight.

Basis

IS 398 (Part 4), Aluminium conductors for overhead transmission purposes: aluminium alloy stranded conductors.

Reference values for planning and comparison. Confirm against the current standard, the purchaser’s specification and the manufacturer’s datasheet before ordering.

AAAC conductor chart (IS 398 Part 4)

CodeArea mm²Wires no./mmDia mmkg/kmUTS kNΩ/km @20 °C
Mole153/2.505.3940.24.332.304
Squirrel227/2.006.0060.26.451.541
Weasel347/2.507.5094.010.110.99
Rabbit557/3.159.45149.216.030.621
Raccoon807/3.8111.43218.323.410.425
Dog1007/4.2612.78272.929.260.339
Dog (Up)12519/2.8914.45342.536.640.2735
Coyote14819/3.1515.75406.943.500.229
Wolf17319/3.4017.00474.050.540.1969
Wolf (Up)20019/3.6618.30549.458.660.171
Panther23219/3.9419.70636.768.050.1471
Panther (Up) 28828837/3.1522.05794.184.710.1182
Panther (Up) 34634637/3.4524.15952.6101.580.0984
Kundah40037/3.7125.971101.6117.400.0829
Zebra46537/4.0028.001280.5136.380.0734
Zebra (Up)52561/3.3129.791448.4146.030.0651
Moose57061/3.4531.051573.7158.660.0598
Morculla60461/3.5531.951666.0167.990.0568
Moose (Up)64261/3.6632.941771.4178.430.0534
Morculla (Up)69561/3.8134.291919.1193.250.0492
Bersimis76761/4.0036.002115.5213.010.0446

Worked example: Panther in AAAC instead of ACSR: what changes

  1. AAAC Panther: 232 mm², 636.7 kg/km, 68.05 kN, 0.1471 Ω/km.
  2. ACSR Panther: 974 kg/km, 89.7 kN, 0.139 Ω/km.
  3. The alloy conductor is 35 % lighter but has a lower breaking load, so sag and tension must be rechecked before substituting.

Is AAAC lighter than ACSR?

Yes, for a similar code. AAAC Panther (232 mm²) is about 637 kg/km against 974 kg/km for ACSR Panther, because AAAC has no steel core. ACSR usually has the higher breaking load.

What does “Up” mean in AAAC codes?

The uprated variants (for example Dog (Up), Wolf (Up), Panther (Up)) are larger-area AAAC constructions listed alongside the base codes, used where utilities want more current capacity on the same route.

What is the resistance of AAAC Zebra?

AAAC Zebra (465 mm², 37 wires of 4.00 mm) has a DC resistance of 0.0734 Ω/km at 20 °C under IS 398 (Part 4).