Motor full load current calculator

Enter the motor’s rated output, supply voltage, power factor and efficiency for its full load current, input power and indicative starting currents, then size the feeder cable with the voltage drop calculator.

Basis

I = P / (√3 × V × cos φ × η) for three-phase motors (V × cos φ × η for single-phase). Starting currents are indicative multiples.

Reference values for planning and comparison. Confirm against the current standard, the purchaser’s specification and the manufacturer’s datasheet before ordering.

Motor full load current at 415 V (0.85 PF, 90 % efficiency assumed)

RatingHPAmps
0.37 kW0.4960.673
0.75 kW11.4
1.1 kW1.52
1.5 kW22.7
2.2 kW2.94
3.7 kW56.7
5.5 kW7.410
7.5 kW10.113.6
11 kW14.720
15 kW20.127.3
18.5 kW24.833.6
22 kW29.540
30 kW40.254.6
37 kW49.667.3
45 kW60.381.8
55 kW73.7100
75 kW100.5136.4
90 kW120.6163.7
110 kW147.5200
132 kW176.9240.1
160 kW214.5291
200 kW268.1363.7
250 kW335.1454.6

Worked example: 37 kW motor at 415 V

  1. Input power = 37 ÷ 0.93 = 39.8 kW.
  2. I = 39,785 ÷ (√3 × 415 × 0.86) = 64.4 A.
  3. Direct-on-line starting is roughly six times that, about 386 A: size the feeder and protection accordingly.

What is the full load current of a 15 kW motor?

At 415 V with 0.85 power factor and 90 % efficiency, about 27.3 A. The rating plate value is the one to design to.

Why is motor current higher than kW alone suggests?

A motor’s rated kW is shaft output. Input power is higher by the efficiency, and the current is higher again by the power factor.

How much current does a motor draw when starting?

Direct-on-line starting typically draws around six to seven times full load current; star-delta starting reduces it to roughly a third of that.