Transformer full-load current and kVA calculator

Full-load current on both windings, the LV short-circuit current from the impedance, and the next common kVA rating for your load with power factor, growth and loading margin. A ready table of full-load currents for common ratings sits below.

Basis

Three-phase relations I = S / (√3 × V) and Isc = I × 100 / Z %; infinite source assumed for fault level.

Reference values for planning and comparison. Confirm against the current standard, the purchaser’s specification and the manufacturer’s datasheet before ordering.

Transformer full-load current table (11 kV / 433 V)

RatingHV A (11 kV)LV A (433 V)
16 kVA0.8421.3
25 kVA1.3133.3
63 kVA3.3184
100 kVA5.25133.3
160 kVA8.4213.3
200 kVA10.5266.7
250 kVA13.12333.3
315 kVA16.53420
400 kVA20.99533.3
500 kVA26.24666.7
630 kVA33.07840
800 kVA41.991,067
1000 kVA52.491,333
1250 kVA65.611,667
1600 kVA83.982,133
2000 kVA1052,667
2500 kVA131.23,333
3150 kVA165.34,200
5000 kVA262.46,667

Worked example: 2000 kVA, 33 kV / 433 V, 6.25 % impedance

  1. LV full-load current = 2,000,000 ÷ (√3 × 433) = 2,667 A.
  2. HV full-load current = 2,000,000 ÷ (√3 × 33,000) = 35 A.
  3. LV fault current ≈ 2,667 × 100 ÷ 6.25 = 42.7 kA with a stiff source.

What is the full-load current of a 1000 kVA transformer?

At 433 V the LV full-load current is about 1333 A; on an 11 kV primary it is about 52.5 A.

How is transformer fault current calculated?

With an infinite source, Isc = full-load current × 100 / %Z. A 1000 kVA, 433 V transformer at 5 % impedance gives about 26.7 kA on the LV side. Source impedance lowers this.

How do I choose the kVA of a transformer?

Divide the maximum demand in kW by the power factor, add load growth, then allow for the loading you want to run at. The calculator rounds up to the next common rating.