Cable size and voltage drop calculator

Enter the load current, run length and cable size to get the voltage drop in volts and percent, the receiving-end voltage and the I²R loss. It also finds the smallest copper or aluminium size that keeps the drop within your limit, for LV feeders and solar DC strings.

Basis

Conductor resistance: IEC 60228 / IS 8130 class 2 maximum DC resistance at 20 °C, corrected to operating temperature.

Reference values for planning and comparison. Confirm against the current standard, the purchaser’s specification and the manufacturer’s datasheet before ordering.

Conductor resistance used (Ω/km)

SizeCu Ω/km 20 °CCu 70 °CCu 90 °CAl Ω/km 20 °CAl 90 °C
1.5 mm²12.114.477615.4287——
2.5 mm²7.418.86619.4485——
4 mm²4.615.51595.8782——
6 mm²3.083.68523.9273——
10 mm²1.832.18962.33343.083.9489
16 mm²1.151.3761.46641.912.4488
25 mm²0.7270.86990.9271.21.5385
35 mm²0.5240.6270.66820.8681.1129
50 mm²0.3870.4630.49350.6410.8218
70 mm²0.2680.32070.34170.4430.568
95 mm²0.1930.23090.24610.320.4103
120 mm²0.1530.18310.19510.2530.3244
150 mm²0.1240.14840.15810.2060.2641
185 mm²0.09910.11860.12640.1640.2103
240 mm²0.07540.09020.09610.1250.1603
300 mm²0.06010.07190.07660.10.1282
400 mm²0.0470.05620.05990.07780.0997
500 mm²0.03660.04380.04670.06050.0776
630 mm²0.02830.03390.03610.04690.0601

Worked example: 100 A over 150 m at 415 V on 50 mm² copper

  1. R at 90 °C = 0.387 × (1 + 0.00393 × 70) = 0.4935 Ω/km; X = 0.08 Ω/km; cos φ = 0.85, sin φ = 0.53.
  2. Vd = √3 × 100 × 0.150 km × (0.4935 × 0.85 + 0.08 × 0.53) = 11.99 V.
  3. 2.89 % of 415 V: within a 3 % limit, so 50 mm² passes on voltage drop. Check current rating separately.

What voltage drop is allowed in a cable?

Many specifications allow 3 % to 5 % from the source to the load for LV circuits, and solar designs often target 1 % to 2 % on DC strings. Use the limit in your project specification or the applicable code.

How is three-phase voltage drop calculated?

Vd = √3 × I × L × (R cos φ + X sin φ), with R the conductor resistance at operating temperature and X the reactance per metre. Single-phase uses 2 instead of √3; DC uses 2 × I × L × R.

Does this calculator check current rating?

No. It sizes by voltage drop only. The cable must also carry the current under its installation conditions, so check the manufacturer’s current rating tables or send us the schedule.